FA-262 Installation & Operator’s Manual
30
8.0 Programming Worksheets
8.1 Entering Programming Mode
Please see “6.0 Programming the FA-265 System” on page 22 for complete instructions.
To enter the Programming mode:
1. Press and hold the Walk Test button for two seconds (located behind the display PCB).
2. Press any button to turn off the trouble buzzer.
3. Press Silence Alarm to scroll through the settings for each programming section (e.g. to change the zone
type, or to turn an option on or off).
4. Press Silence Trouble to move to the next programming section (e.g. to move from zone 1 to zone 2).
5. The panel will indicate the current programming section using the Common Trouble LEDs, as shown
below.
Please see “6.2 Programming Section Descriptions” on page 24 for detailed descriptions of each
programming section.
Note: All zone alarms must be reset prior to entering the programming mode. While the panel is in the
programming mode, the annunciators will show a trouble condition.